English
Product name: Rack-mounted LiFePo4 battery, manufactured with Grade A Lifepo4 Prismatic Cell
Product Parameter:
1: Product name: Rack-mounted LiFePo4 battery, manufactured with Grade A Lifepo4 Prismatic Cell
2: BMS Built-in: Smart 16S 200A BMS, reliable BMS System with circuit breaker and Air circuit breaker.
A: circuit breaker: communication with BMS, with protection functions with short circuit protection, voltage protection, current protection, capacity protection, temperature protection, equalization function
B: Air circuit breaker: If the current in the circuit exceeds the rated current switch that will automatically disconnect
3: Maximum Discharge: 200A
4: Maximum Charge: 200A
5: Display: LCD screen
6: Switch: ON/OFF switch, Reset switch: Reduce BMS self-damage and reset
7: Connection: Max. 16 Unit in Parallel
8: Communication protocol: RS485/RS232/CAN
9: Charging Temperature: 0~45°C (32~113°F)
10: Discharging Temperature: -20~60°C (-4~140°F)
11: Cycle Life: ≥6000 Cycles
12: Weight: 96Kg
13: Dimension(Length* Width*Height): 480*484*225mm
Case Structure of Battery Pack
No. | Item | Functional Description | Remark |
1 | Battery+ | Positive terminal | |
2 | Battery- | Negative terminal | |
3 | With LCD | ||
4 | With LCD | ||
5 | Handle | ||
6 | Hanger | For mounting the battery pack | |
7 | Switch | ON/OFF | |
8 | RST | On/OFF /Reset button | |
9 | RUN | Working indicator light | Display state information |
10 | ALM | ALM alarm indicator light | Red-trouble-light on |
11 | ADS | Battery address dialer | Display connection address |
12 | CAPACITY | Capacity volume indicator | Display the battery's capacity |
13 | Dry contact | DO | Normal close |
14 | RS485 | RS485 communication interface | RS485connection port-A |
15 | CAN port | CAN | CAN communication port |
16 | RS232 port | RS232 | RS232 communication port |
17 | RS485 port | RS485B |
Battery Pack Specification
No. | Item | General Parameter | Remark | |
1 | Combination method | 16S2P | ||
2 | Rated Capacity | Typical | 200Ah | Standard discharge after Standard charge(package) |
Minimum | 200Ah | |||
3 | Factory Voltage | 48V-49.5V | Mean Operation Voltage | |
4 | Voltage at end of Discharge | 42V | Discharge Cut-off Voltage | |
5 | Charging Voltage | 54V | ||
6 | Internal Impedance |
≤20mΩ Internal resistance measured at AC 1KHZ after 50% charge |
The measure must uses the new batteries that within one week after shipment and cycles less than 5 times | |
7 | Standard charge | Constant Current 40A, Constant Voltage see No.5 0.02CA cut-off. | Charge time: Approx 6 h | |
Limiting current | 20A | |||
8 | Standard discharge | Constant current: 40A, end voltage see NO.4 | ||
9 | Maximum Continuous Charge Current | 100A | T≥10ºC | |
10 | Maximum Continuous Discharge Current | 100A | T≥10ºC | |
11 | Operation Temperature Range | Charge: 0~45℃ | 60±25%R.H. Bare Cell | |
Discharge : -20~55℃ | ||||
12 | Storage Temperature Range | Less than 12 months: -10~35℃ | 60±25%R.H. at the shipment state | |
Less than 3 months: -10~45℃ | ||||
Less than 7 day: -20~65℃ | ||||
13 | Dimensions | 442*620*222mm | Include case | |
14 | Weight | 87.5kg | Include case |